8 Operation at Use of a PC
8.3 Configuration of the Device
181
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Changing the Report Configuration
To change the report configuration, proceed as follows:
✧
In the navigation window of the
Recording and Reporting
menu click
Report configuration
.
Figure 8-50
Configure Tab, Report Configuration Input/Output Window (Excerpt)
✧
Use the buttons to select the evaluation mode or enter the user-defined mode into the fields according to
Table 8-18.
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
Activation
of the device configuration
according to section
Activating the Set of Parameters
. If you want to change other settings, enter the
changes and then enable the device configuration as described in section
.
NOTE
The chapter 8.4.2.4 describes the output of the power quality report.