
8 Operation at Use of a PC
8.3 Configuration of the Device
184
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.6.8
Transient Detection
Default Settings and Setting Ranges
Parameterizing the Transient Detection
If you want to change the
Transient reference level
, proceed as follows:
✧
In the navigation window of the
Recording and Reporting
menu, click the element
Transient reference
level.
Figure 8-52
Configure tab, transient reference level input/output window
✧
Change the parameter according to Table 8-16.
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
Activation
of the device configuration
according to section
Activating the Set of Parameters
. If you want to change other settings, enter the
changes and then enable the device configuration as described in section
Table 8-20
Transient Detection
Parameter
Default Setting
Setting Range
Transient reference level
110 %
110 % to 240 % of
the
nominal/declared supply
voltage