8 Operation at Use of a PC
8.5 Maintenance
259
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.5.4.3
Audit Log
The device provides an audit log to track the security-relevant events. A dedicated password is required to view
the audit log. Only a user with the auditor rights can access it.
The
Audit log
is located in the
Maintenance
tab. To view the
Audit log
, proceed as follows:
✧
In the navigation window, select the
Message
logs
menu and click
Audit log
.
Figure 8-108
Maintenance Tab, Access Audit Log
✧
Enter the audit log password into the
Password
field.
✧
Click
Display
.
Audit messages are displayed on the HTML pages.
Figure 8-109
Maintenance Tab, Display Audit Log
To refresh the display of the audit log, click
Audit log
or press F5, and enter the audit log password again.
NOTE
The audit log is only available via HTML pages, not via the device display.
The audit log stores the latest 2048 audit messages. The older messages are automatically overwritten.
You cannot delete the audit messages manually.
For a new delivered device, audit logs created during production process are kept.