13 Technical Data
13.2 Test Data
328
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
EMC Tests for Immunity (Type Tests)
EMC Test for Noise Emission (Type Test)
Standards:
IEC EN 61000-6-2
For more standards see also individual
functions
Electrostatic discharge, Class III,
IEC 61000-4-2
6 kV contact discharge; 8 kV air discharge,
both polarities; 150 pF; R
i
= 330
with connected Ethernet cable
High frequency electromagnetic field, amplitude-modulated,
Class III
IEC 61000-4-3
10 V/m; 80 MHz to 3 GHz; 80 % AM; 1 kHz
Fast transient bursts, Class III
IEC 61000-4-4
2 kV; 5 ns/50 ns; 5 kHz;
Burst length = 15 ms;
Repetition rate 300 ms;
Both polarities;
R
i
= 50
;
Test duration 1 min
High energy surge voltages (SURGE), Installation Class III
IEC 61000-4-5
Impulse: 1.2 µs/50 µs
Auxiliary voltage
Common mode: 2 kV; 12
; 9 µF
Diff. mode:1 kV; 2
; 18 µF
Measuring inputs, binary inputs, and
relay outputs
Common mode: 2 kV; 42
; 0.5 µF
Diff. mode: 1 kV; 42
; 0,5 µF
Line-conducted high frequencies, amplitude-modulated, Class
III
IEC 61000-4-6
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
Power system frequency magnetic field
IEC 61000-4-8, Class IV;
30 A/m continuous; 300 A/m for 3 s
1 MHz test, Class III, IEC 61000-4-18
2.5 kV (peak); 1 MHz;
= 15 µs;
400 Surges per s;
Test duration 1 min; R
i
= 200
Standard:
IEC EN 61000-6-4
Disturbance voltage to lines, only auxiliary voltage
IEC-CISPR 22
150 kHz to 30 MHz Limit Class A
Disturbance-field strength
IEC-CISPR 22
30 MHz to 1000 MHz Limit Class A