
9 Operation at Use of the Display
9.4 Parameterization
294
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
1)
After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later re-open these connections.
Current - Deadband
5 %
1 % to 5 % in increments of 1 %
Power - Deadband
5 %
1 % to 5 % in increments of 1 %
Power factor - Deadband
5 %
2% to 5 % in increments of 1 %
Frequency - Deadband
0,05
0.02 %
0.05 %
Table 9-8
Serial Communication Settings – Modbus RTU and Modbus RTU Master Bus Protocols
Parameter
Default Setting
Setting Range
Bus protocol
Modbus RTU
None
Modbus RTU
Modbus Master
Bus Protocol Modbus RTU
(Slave)
Device address
1
1 to 247
Baud rate
19 200 bit/s
For the selection, see Chapter 15
Parity
Even
For the selection, see Chapter 15
Access rights
Full
Full
Read only
Communication supervision time
600 * 100 ms
0 s = none
100 ms to 6 553 400 ms
Bus Protocol Modbus RTU Master
Baud rate
19 200 bit/s
For the selection, see Chapter 15
Parity
even
For the selection, see Chapter 15
Additional inter-character timeout
1 ms
0 ms to 100 ms
Maximum 0x/1x register gap
40
0 to 200
Maximum 3x/4x register gap
10
Table 9-7
Ethernet Communication Settings (cont.)