8 Operation at Use of a PC
8.3 Configuration of the Device
134
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.1.3
Finish Configuration
When you have changed the configuration, you must either enable it as the active set of parameters or save it.
Activating the Set of Parameters
To
activate
the set of parameters, proceed as follows:
✧
In the navigation window, select the
Finish configuration
menu and click
Activation
.
Figure 8-19
Configure Tab, Activation Input/Output Window
✧
In the
Activation
input/output window, enter the valid activation password into the
password
field.
chapter 8.3.7.6 explains how to set the activation password.
✧
Click
Activation
.
At first the message
Parameter activation is still in progress
will be shown and then the message
Parameter activation is complete
in the input/output window.
The modified set of parameters is loaded as the active set of parameters into the device and the new
parameters take effect immediately.
If the password is wrong, this message appears:
The password is wrong. Please enter the correct
password.
The
Action was not successful
indication (red) is displayed on the status bar.