8 Operation at Use of a PC
8.3 Configuration of the Device
169
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
1)
The
Detection mode
will always synchronize with the setting of
Record ph-ph voltage
under
Waveform
capture setting
.
Parameterizing the Trigger Management
To change the
trigger management
settings, proceed as follows:
✧
In the navigation window, select the
Recording and Reporting
menu and click
Trigger management
.
Figure 8-44
Configure Tab, Trigger Management Input/Output Window
✧
Select the respective parameters in the list boxes according to Table 8-13.
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
Activation
of the device configuration
according to section
Activating the Set of Parameters
. If you want to change other settings, enter the
changes and then enable the device configuration as described in section
.
Total recording duration
2.0 s
0.2 s to 3.0 s in 0.2-s steps
Pretrigger ratio
10 %
0 % to 30 % in 5-% steps
Record ph-ph voltage
no
no
yes
Table 8-13
Trigger Management