8 Operation at Use of a PC
8.5 Maintenance
256
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
✧
Enter the maintenance password into the
Password
field.
✧
Click
Delete load profile buffer
.
The load profile buffer is deleted. The
Action was successful
indication is displayed on the status bar.
8.5.3.5
Events
To reset the PQ events, proceed as follows:
✧
In the navigation window, select the
Presets
menu and click
Events
.
Figure 8-105
Maintenance Tab, Events Default Setting
✧
Select the events you want to reset using the option fields.
✧
Enter the maintenance password in the
Password
field.
✧
Click
Reset PQ events
.
The selected PQ events are reset. The
Action was successful
indication is displayed on the status bar.