13 Technical Data
13.1 General Device Data
322
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Inputs for Alternating Current Measurements, Connector Block E - Cat III
Binary Inputs, Connector Block U - Cat III
Binary Outputs, Connector Block G - Cat III
Input alternating currents
Rated input current range
AC 1 A to 5 A (autorange)
Max. input current
AC 10 A
Power consumption per input
at 5 A
100 mVA
Further information about the current measuring inputs
Max. rated input voltage
150 V
Measuring error under environmental influences:
see technical data
acc. to IEC 61000-4-30 Ed. 3 Class A (0.1 %)
Thermal stability
10 A continuous
100 A for max. 1 s
Sampling rate
10.24 kHz
Maximum input voltage
DC 300 V
Static input current
1.34 mA ± 20 %
UIL min (at threshold voltage 19 V)
DC 14 V
UIL max (at threshold voltage 19 V)
DC 19 V
UIL min (at threshold voltage 88 V)
DC 66 V
UIL max (at threshold voltage 88 V)
DC 88 V
UIL min (at threshold voltage 176 V)
DC 132 V
UIL max (at threshold voltage 176 V)
DC 176 V
Progagation delay low to high
2.8 ms ± 0.3 ms
Maximum contact voltage
Alternating voltage
230 V
Direct voltage
250 V
Maximum currents
Maximum continuous contact current
100 mA
Maximum pulse current for 0.1 s
300 mA
Further information about the binary outputs
Internal impedance
50
Admissible switching frequency
10 Hz