
8 Operation at Use of a PC
8.3 Configuration of the Device
186
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Parameterizing the Time Synchronization
To change the time synchronization, proceed as follows:
✧
In the navigation window, select the
Administrative
menu and click
Time synchronization
.
Figure 8-53
Configure Tab, Time Synchronization Input/Output Window, Ethernet NTP Selected
✧
Enter the desired values in the fields and select the parameters in the list boxes and in the option field as
described in Table 8-21.
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
Activation
of the device configuration
according to section
Activating the Set of Parameters
. If you want to change other settings, enter the
changes and then enable the device configuration as described in section
Error indication after
10 min
2 min to 120 min
Additional Parameter if the Source is Fieldbus (Modbus RTU and IEC 60870-5-103)
Error indication after
10 min
2 min to 120 min
Table 8-21
Time Synchronization Settings (cont.)
Parameter
Default Setting
Setting Range