Commissioning
6.4 Modbus address register
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
95
Address
Number
of regis-
ters
Format
Access
Unit
Factor
Measured variable
Hex
Decimal
1BF2 7154
2
–
–
–
–
–
1BF4 7156
2
UINT32
R
varh
1.0
T1 Reactive energy L3 - Export
1BF6 7158
2
–
–
–
–
–
1BF8 7160
2
–
–
–
–
–
1BFA 7162
2
–
–
–
–
–
1BFC 7164
2
UINT32
R
Wh
1.0
T2 Active energy L3 - Import
1BFE 7166
2
–
–
–
–
–
1C00 7168
2
UINT32
R
Wh
1.0
T2 Active energy L3 - Export
1C02 7170
2
–
–
–
–
–
1C04 7172
2
UINT32
R
varh
1.0
T2 Reactive energy L3 - Import
1C06 7174
2
–
–
–
–
–
1C08 7176
2
UINT32
R
varh
1.0
T2 Reactive energy L3 - Export
1C0A 7178
2
–
–
–
–
–
Hour counter
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
ters
Format
Access
Unit
Factor
Measured variable
Hex
Decimal
1E00 7680
2
UINT32
R
s
1.0
Partial operating hours counter 1
1E02 7682
2
UINT32
R
s
1.0
Partial operating hours counter 2
1E04 7684
2
UINT32
R
s
1.0
Partial operating hours counter 3
Parameter setup
Note
Write commands are only possible with the 7KT1665 80 A, Modbus RTU (not MID)
Parameters are read and changed in accordance with the following rules:
Address
Number
of regis-
ters
Format
Access
Unit
Factor
Measured variable
Hex
Decimal
5000 20480
1
UINT16
RW
–
–
Menu Number selection
1)
5002 20482
1
UINT16
RW
–
–
Parameter Number selection
1)
5004 20484
1 … 28 UINT16
RW
–
–
Parameter value
2)
2F01 12033
1
UINT16
W
–
0.1
Write to Flash memory
1)
1
Accessed via the function codes 0x04 (read) or 0x06 (write).
2
Accessed via 0x04 (read), 0x06 (write), or 0x16 (multiwrite).