Commissioning
6.4 Modbus address register
7KT16 energy meter
88
Equipment Manual, 09/2020, 2514284147-04
Address
Number
of regis-
ters
Format
Access
Unit
Factor
Measured variable
Hex
Decimal
1E84 7812
4
UINT64
R
Wh
10.0
Partial active energy L3 - Import
1E88 7816
4
UINT64
R
Wh
10.0
Partial active energy L3 - Export
1E8C 7820
4
UINT64
R
varh
10.0
Partial reactive energy L3 - Import
1E90 7824
4
UINT64
R
varh
10.0
Partial reactive energy L3 - Export
1E94 7828
4
UINT64
R
VAh
10.0
Partial apparent energy L3
Hour counter
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
ters
Format
Access
Unit
Factor
Measured variable
Hex
Decimal
1E00 7680
2
UINT32
R
s
1.0
Total operating hours counter
1E02 7682
2
UINT32
R
s
1.0
Partial operating hours counter 1
1E04 7684
2
UINT32
R
s
1.0
Partial operating hours counter 2
1E06 7686
2
UINT32
R
s
1.0
Partial operating hours counter 3
1E08 7688
2
UINT32
R
s
1.0
Partial operating hours counter 4
Status
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
ters
Format
Access
Unit
Factor
Measured variable
Hex
Decimal
2140 8512
1
UINT16
R
BOOL
–
OR across all limits *1
2141 8513
1
UINT16
R
BOOL
–
Limit 1
2142 8514
1
UINT16
R
BOOL
–
Limit 2
2143 8515
1
UINT16
R
BOOL
–
Limit 3
2144 8516
1
UINT16
R
BOOL
–
Limit 4
2145 8517
1
UINT16
R
BOOL
–
Limit 5
2146 8518
1
UINT16
R
BOOL
–
Limit 6
2147 8519
1
UINT16
R
BOOL
–
Limit 7
2148 8520
1
UINT16
R
BOOL
–
Limit 8
1
Example: If the value (hex) =0x05, inputs 1 and 3 are active.