Description
3.5 Three-phase devices 5 A
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
45
3.5.2
Advanced functions
Procedure
1.
Press both the "Increase" and "Decrease" keys simultaneously from any display.
The device changes to the
Menu
display.
2.
Press "Increase" or "Decrease" key to change to the
Set
display.
3.
Confirm your selection by pressing the "Next" key.
Enter password
appears on the display
.
4.
Confirm your selection by pressing the "Next" key.
5.
Enter the password.
Press "Increase" or "Decrease" to change the flashing digit.
Confirm your digit selection by pressing the "Next" key.
–
If the password is incorrect,
PASS Er
appears on the display
.
Press the "Next" key.
Enter the password again.
–
If the password is correct,
Advanced password ok
appears on the display.
Press the "Next" key.
6.
The first entry in the following list appears on the display:
–
CLEAR P
: Clear partial energy meters
–
CLEAR h
: Clear partial hour counter (if activated)
–
CLEAR d
: Clear maximum demand values (if activated)
–
ET-DEF
: Set all parameters to the default values.
–
SETUP
: Parameter programming (setup)
–
INFO
: Revision and checksum of internal software
–
ESC
: Return to normal mode
Press the "Increase" or "Decrease" key to scroll through the list.
7.
Press the "Next" key to select a function.
Note
If you do not press the keys for more than 120 s, the menu closes automatically.