Description
3.5 Three-phase devices 5 A
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
59
P07.01 Primary address for M-Bus network
P07.02 Secondary address for M-Bus network
P07.03 Speed of communication
P08 Limit thresholds (LIMn, n = 1 to 4)
Note
This menu is divided into 4 sections for limit thresholds LIM 1 ... 4 in P08.n.01. The menu
defines the energy meter measurement to which the limit threshold applies.
Unit
Default
Range
P08.n.01 Reference measure
–
OFF
OFF … (measures)
P08.n.02 Function
Max
•
Max
•
Min
•
Max + Min
P08.n.03 Upper threshold
0
−
9999 … +9999
P08.n.04 Multiplier
x1
/100 … x10k
P08.n.05 Delay
s
0
0.0 … +1000.0
P08.n.06 Lower threshold
–
−
9999 … +9999
P08.n.07 Multiplier
x1
/100 … x10k
P08.n.08 Delay
s
0
0.0 … +1000.0
P08.n.09 Status
–
OFF
•
OFF
•
ON
P08.n.10 Reset mode
P08.n.02 Defines the energy meter measurement to which the limit threshold applies.
•
Max
= LIMn active if the measurement exceeds P08. P08.n.03 is the reset
threshold.
•
Min
= LIMn active if the measurement falls below P08. P08.n.06 is the reset
threshold.
•
Min + Max
= LIMn active if the measurement exceeds P08.n.03 or falls below
P08.n.06.
P08.n.03
,
P08.n.04
Defines the upper threshold resulting from the multiplication of the value P08.n.03
by P08.n.04.
P08.n.05 Triggering delay for upper threshold.
P08.n.06
,
P08.n.07
Defines the lower threshold resulting from the multiplication of the value P08.n.06
by P08.n.07.
P08.n.08 Triggering delay for lower threshold.
P08.n.09 Permits inversion of the status of limit threshold LIMn.
P08.n.10 •
ON
= Threshold value is saved and must be reset manually.
•
OFF
= Threshold value is saved and is reset automatically.