Description
3.3 Single-phase devices
7KT16 energy meter
24
Equipment Manual, 09/2020, 2514284147-04
3.3.4.4
Setup parameter table
For all single-phase devices
Code
Description
Default Range
P-01
Password
0000
0000 … 9999
P-02
Activate programmable limit thresh-
old
OFF
•
OFF
•
THR
P-03
Limit threshold
kW
•
01 = kW
•
02 = kvar
•
03 = V
•
04 = A
•
05 = Hz
•
06 = kWh part
•
07 = h part
•
08 = kW demand
P-04
Threshold ON
100.00 0.00 … 999.99
P-05
Delay ON
5 s
0 … 9999 s
P-06
Threshold OFF
50.00 0.00 … 999.99
P-07
Delay OFF
5 s
0 … 9999 s
P-08
Activate hour counter
OFF
•
OFF
•
ON
•
THR
P-09
Activate demand values
OFF
•
OFF
•
ON