Commissioning
6.4 Modbus address register
7KT16 energy meter
90
Equipment Manual, 09/2020, 2514284147-04
Wiring test results
Address
Number
of regis-
ters
Format
Access
Active bit Measured variable
Hex
Decimal
1F20 7968
2
UINT32
R
0
Voltage L1N
UINT32
R
1
Voltage L2N
UINT32
R
2
Voltage L3N
UINT32
R
3
Current L1
UINT32
R
4
Current L2
UINT32
R
5
Current L3
UINT32
R
6
Incorrect phase sequence
UINT32
R
7
Phase unbalance
UINT32
R
8
Current transformer L1 inverted
UINT32
R
9
Current transformer L2 inverted
UINT32
R
10
Current transformer L3 inverted
UINT32
R
11
Current transformers L1 to L2
UINT32
R
12
Current transformers L1 to L3
UINT32
R
13
Current transformers L2 to L1
UINT32
R
14
Current transformers L2 to L3
UINT32
R
15
Current transformers L3 to L1
UINT32
R
16
Current transformers L3 to L2
The wiring is correct if the result is 0 or no bit is active.
Parameter setup
Parameters are read and changed in accordance with the following rules:
Address
Number
of regis-
ters
Format
Access
Unit
Factor
Measured variable
Hex
Decimal
5000 20480
1
UINT16
RW
–
–
Menu Number selection
1)
5001 20481
1
UINT16
RW
–
–
Menu Number selection
1)
5002 20482
1
UINT16
RW
–
–
Parameter Number selection
1)
5004 20484
1 … 28
UINT16
RW
–
–
Parameter value
2)
2F01 12033
1
UINT16
RW
–
0.1
Write to Flash memory
1)
1)
Accessed via the function codes 0x04 (read) or 0x06 (write).
2)
Accessed via 0x04 (read), 0x06 (write), or 0x16 (multiwrite).