Description
3.4 Three-phase devices 80 A
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
41
Setup
Unit of meas-
urement
Measured value
18
V L2
Phase voltage L2N
19
V L3
Phase voltage L3N
20
V L-L
Phase-to-phase voltage
1)
21
V L1L2
Phase-to-phase voltage L1L2
22
V L2L3
Phase-to-phase voltage L2L3
23
V L3L1
Phase-to-phase voltage L-L1
24
A
Voltage
1)
25
A L1
Voltage L1
26
A L2
Voltage L2
27
A L3
Voltage L3
28
PF
Power factor
1)
29
PF
Power factor (total)
30
PF L1
Power factor L1
31
PF L2
Power factor L2
32
PF L3
Power factor L3
33
HZ
Frequency
34
kWh+ part
Partial active energy
35
kWh+ L1 part
Partial active energy L1 (import)
36
kWh+ L2 part
Partial active energy L2 (import)
37
kWh+ L3 part
Partial active energy L3 (import)
38
kWh− part
Partial active energy (export)
39
kWh− L1
part
Partial active energy L1 (export)
40
kWh− L2
part
Partial active energy L2 (export)
41
kWh− L3
part
Partial active energy L3 (export)
42
kWh+ part
Partial reactive energy (import)
43
kWh+ L1 part
Partial reactive energy L1 (import)
44
kWh+ L2 part
Partial reactive energy L2 (import)
45
kWh+ L3 part
Partial reactive energy L3 (import)
46
kWh−
part
Partial reactive energy (export)
47
kWh− L1
part
Partial reactive energy L1 (export)
48
kWh− L2
part
Partial reactive energy L2 (export)
49
kWh− L3
part
Partial reactive energy L3 (export)
50
kW d
Active power demand values
1)
If limit thresholds are used for these measurements, the comparison is performed based on the
highest or the lowest of the three phases, depending on the type of limit (maximum or minimum).
Example:
If a maximum limit threshold is defined for the phase voltages, the limit is activated if one of the three
voltages is above the limit threshold.