Commissioning
6.4 Modbus address register
7KT16 energy meter
82
Equipment Manual, 09/2020, 2514284147-04
4.
Check the device parameters and adjust them if necessary.
Note
You can only change parameters in offline mode.
You can find more information on parameterization in the powerconfig Online Help.
5.
In the "Parameters" window, click the "Load to device" button.
The set parameters are loaded to the device.
6.4
Modbus address register
6.4.1
Modbus address table for single-phase devices with Modbus interface
Continuous measured values
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
ters
Format
Access
Unit
Factor
Measured variable
Hex
Decimal
0002 2
2
UINT32
R
V
0.01
Voltage
0004 4
2
–
–
–
–
–
0006 6
2
–
–
–
–
–
0008 8
2
UINT32
R
A
0.001
Current
000A 10
2
–
–
–
–
–
000C 12
2
–
–
–
–
–
000E 14
2
–
–
–
–
–
0010 16
2
–
–
–
–
–
0012 18
2
–
–
–
–
–
0014 20
2
INT32
R
W
10.0
Active power
0016 22
2
–
–
–
–
–
0018 24
2
–
–
–
–
–
001A 26
2
INT32
R
var
10.0
Reactive power
Range limit
0026 38
2
INT32
R
–
0.01
Power factor
Range limit
0032 50
2
INT32
R
Hz
0.1
Frequency