Description
3.3 Single-phase devices
7KT16 energy meter
20
Equipment Manual, 09/2020, 2514284147-04
5.
Press the front key (> 3 s) to confirm and return to the parameter code selection.
ESC
appears on the display after the last parameter code.
6.
Press the front key (> 3 s).
The parameters are saved. The system resumes normal operation.
3.3.2
Advanced functions
Procedure
1.
Press the front key from any display (> 5 s).
–
If password protection is activated,
PASS
appears on the display. Proceed to point 2
(password entry).
–
If password protection is deactivated, (factory setting, default password = 0000),
proceed to point 5 (function selection).
2.
Release the key.
The device shows
0000
after approx. 2 to 3 seconds. The device is waiting for the
password to be entered.
3.
Enter the password. Press the front key to increase the flashing digit in each case.
After 3 seconds, the entry field jumps to the next position.
4.
After entering the password, press the front key to confirm.
–
If the password is incorrect,
PASS Er
appears on the display and the normal display
reappears.
–
If the password is correct, proceed to the next point.
5.
The first entry in the following list of functions appears on the display:
–
CLEAR P
: Clear partial energy meters
–
CLEAR h
: Clear partial hour counter (if activated)
–
CLEAR d
: Clear maximum demand values (if activated)
–
SETUP
: Parameter programming (setup)
–
INFO
: Revision and checksum of internal software
–
ESC
: Return to normal display
Press the front key briefly to scroll through the list.
6.
To select a function, press the front key for > 3 s while the function is visible on the display.
Note
If you keep the front key pressed for longer than 60 s, the menu closes automatically.