Commissioning
6.3 Parameterizing with powerconfig
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
81
5.
Select PAC1600 in the
Search for device
option.
6.
Enter the communication parameters:
–
COM port
–
Address
–
Baud rate
–
Format
–
Protocol
7.
Click the
Start search
button.
All devices found are shown in the "Result" window.
8.
Select the required device.
9.
Click the
Create devices
button.
The selected device is added.
10.
In the
Views
menu, select the submenu "Parameters".
The "Parameters" window is displayed.
11.
In the "Properties" window, click the
Load to PC
button.
The configuration is loaded from the device to the PC.
Parameterizing the device
The parameters are entered and changed in offline mode.
To switch between online and offline mode, click
Activate online view
in the
Options
menu
or press the F12 key.
Set the required basic parameters.
Make use of the Online Help in powerconfig.
In order to load the parameters to the device, proceed as follows:
1.
Integrate the device in powerconfig.
2.
In the
Views
menu, select the submenu
Parameters
or alternatively press the "Ctrl" and
"Pos1" keys simultaneously.
The "Parameters" window is displayed.
3.
In the "Parameters" window, click the
Load to PC
button.
The set parameters are loaded to the device.