Description
3.4 Three-phase devices 80 A
7KT16 energy meter
38
Equipment Manual, 09/2020, 2514284147-04
3.4.4.5
Setup parameter table for devices with S0 interface
Device-dependent parameters
Code
Description
Default Range
P1-01
Password
0000
0000 … 9999
P2-01
Function of output 1
10 PUL/k
Wh
•
OFF = Deactivated
•
1000 PUL/kWh
•
100 PUL/kWh
•
10 PUL/kWh
•
1 PUL/kWh
•
THR = Programmable limit thresholds
P2-02
Measured variable for output 1 limit
01 kW See Settable values for parameters
P2.01, P3.01, P4.01 (Page 40).
P2-03
Limit 1 ON
100.00 0.00 … 999.99
P2-04
Delay 1 ON
5 s
0 … 9999 s
P2-05
Limit 1 OFF
50.00 0.00 … 999.99
P2-06
Delay 1 OFF
5 s
0 … 9999 s
P3-01
Function of output 2
OFF
•
OFF = Disabled
•
1000 PUL/kWh
•
100 PUL/kWh
•
10 PUL/kWh
•
1 PUL/kWh
•
THR = programmable thresholds
P3-02
Measured variable for output 2 limit
01 kW See Settable values for parameters
P2.01, P3.01, P4.01 (Page 40).
P3-03
Limit 2 ON
100.00 0.00 … 999.99
P3-04
Delay 2 ON
5 s
0 … 9999 s
P3-05
Limit 2 OFF
50.00 0.00 … 999.99
P3-06
Delay 2 OFF
5 s
0 … 9999 s
P4-01
Function of input 1
OFF
•
OFF = Deactivated
•
ON = Activated
•
TAR = Tariff selection
•
CLr Part = Clear partial energy meter
•
CLr Hr = Clear hour counter
•
CLr dE = Clear max. demand values