Description
3.5 Three-phase devices 5 A
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
63
P14 Outputs (OUT1 and OUT2) only for devices with S0 interface/digital outputs
Note
This menu is divided into two sections for outputs OUT1 and OUT2.
Unit
Default
Range
P14.n.01 Output function
–
OFF
•
OFF
•
Wh+
•
Wh−
•
varh+
•
varh−
•
VAh
P14.n.02 Channel number
1
1 … 4
P14.n.03 Normal status
OFF
•
OFF
•
ON
P14.n.04 Delay "ON"
s
0.0
0.0 … 6000.0
P14.n.05 Delay "OFF"
0.0
P14.n.01 Output function:
•
OFF =
Output deactivated.
•
ON =
Output is always activated when the measuring device is switched on.
•
SEQ =
Output activated in the event of phase sequence error.
•
LIM - ALA
=
Output activated in the event of upward violation of limit or
alarm.
•
PUL =
Output used as pulse generator as per P11.
P14.n.03 Output of normal status. Permits inversion of activation logic.
P14.n.04 Delay setting for "ON".
P14.n.05 Delay setting for "OFF".