Description of the OEM settings
15.07.2002
General values
6.10 Software
version
•
Straightforward display of software version used, without removing the controller
The software version installed represents the state of the software available at the time
the controller was produced.
1. Press the line selection buttons to select line 91
OEM
.
2. No setting can be made with the + / - buttons.
Display
Unit
00.0 ... 99.9
Digits
The software version will automatically be displayed on this line.
Example: 01.0
The first 2 digits give the software version (01.)
The third digit gives the software revision
(.0)
6.11 Device
operating
hours
•
Display of the number of device operating hours
Here, you can read the number of hours the controller has been in operation
1. Press the line selection buttons to select operating line 92
OEM
.
2. No setting can be made with the + / - buttons.
Display
Unit
0... 500‘000
h
The number of operating hours since the controller was first commissioned will
automatically be displayed on this line.
The hours considered as operating hours are those during which power was supplied to
the controller, that is, including the periods of time with no effective heating operation.
The number of operating hours cannot be reset.