42/166
Siemens Building Technologies
Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Description of the enduser settings
15.07.2002
D.h.w. values
3.11
Nominal d.h.w. temperature setpoint
•
D.h.w. heating only if there is a demand for it
•
Possibility of using 2 different d.h.w. temperature setpoints
1. Press the operating line selection buttons to select line 13.
2. Press the + / – buttons to adjust the nominal setpoint of the d.h.w. temperature.
Setting range
Unit
Factory setting
TBWR...TBWmax °C
55
TBWR
Reduced setpoint of d.h.w. temperature (setting on operating line 120)
TBWmax
Maximum nominal setpoint of d.h.w. temperature (setting on line 40
OEM
)
0 10 20 30 40 50 60 70 80 90 100 120 130 140 °C
23
79
Z1
6
The temperature setpoint during normal d.h.w. operation will be changed.
13
Setting "Nominal setpoint of the d.h.w. temperature”
120
Setting "Reduced setpoint of the d.h.w. temperature”
40
OEM
Setting "Maximum nominal setpoint of the d.h.w. temperature”
D.h.w. heating has 2 different setpoints that can be used:
•
Nominal d.h.w. temperature setpoint: It ensures the d.h.w. temperature required
during main occupancy times
•
Reduced d.h.w. temperature setpoint (setting on operating line 120): it ensures the
d.h.w. temperature required during the main occupancy times.
The criteria required for releasing d.h.w. heating are defined by the settings made on
lines 121 and 123 and 124.
In the event of a sensor with a short-circuit (display ”- - -” in input test, test step 1) the
d.h.w. will not be heated (protection against scalding).
Benefit
Setting
Effect
D.h.w. temperature
setpoints
D.h.w. charging
Note