149/166
Siemens Building Technologies
Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Application examples
15.07.2002
8.5
Plant types RVA47.320 - no. 31
The plant type no. is identical with the number displayed on line 53.
Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating with
charging pump through the RVA47.320.
System pump for heating circuits and d.h.w. heating connected to RVA47.320.
4
1
2
3
B10
B70
23
79
S3
1
B3
Type of unit
BMU 1
BMU 2
BMU 3
BMU 4
RVA47.320
Display of plant type
31
Heating curve (line 17)
--- (inactiv) or 2.5...40
Pump function Q1 (line 95)
3 (primary pump for HC and d.h.w.)
Heat generation is released by the heat demand signal from a consumer (or d.h.w.
heating):
•
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
•
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).
L
N
Q1
F1
N1
Q3
B3
B3
B9
B7
B70
M
L
N
23
79A
31
MB
LPB
MD
A6 / BMU
PPS
DB
B10
B
M
B
M
H1
B10
B
M
B9
B
M
A6
B
M
H1
For a detailed legend, refer to page 158.
Note
Hydraulic circuit
Important
Electrical connections
Legend