115/166
Siemens Building Technologies
Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Description of the OEM settings
15.07.2002
Heating circuit values
5.6
Gain factor of room influence (KORR)
•
The influence of room temperature deviations on the controlled system can be
adjusted
Defines the influence of room temperature setpoint deviations on the controlled system.
The room influence can be activated and deactivated (operating line 101).
1.
Press the line selection buttons to select operating line 30OEM.
2.
Press the + / – buttons to set the gain factor.
Setting range
Unit
Factory setting
0...20 -
4
Changing this setting has the following impact:
Entry:
Increase:
Authority of room influence will increase
Decrease:
Authority of room influence will decrease
The value of setting 30
OEM
is divided by 2 and multiplied by the differential (room
temperature setpoint – actual room temperature).
The result is then added to the room temperature setpoint.
TRx)
-
(TRw
2
30
+
TRw
=
TRwk
OEM
TRw Room temperature setpoint
TRx Actual value of the room temperature
TRwk Corrected room temperature setpoint
The gain factor of the room influence is only active when a room unit is connected.
Benefit
Note
Setting
Effect
Correction
Note