153/166
Siemens Building Technologies
Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Application examples
15.07.2002
8.9
Plant types RVA47.320 - no. 35
The plant type no. is identical with the number displayed on line 53.
Control of a single BMU or cascade control of up to four BMUs. Control of the pump
heating circuit by the RVA47.320. D.h.w. heating with charging pump by the
RVA47.320.
4
1
2
3
B10
B70
23
79
S
35
B3
Type of unit
BMU 1
BMU 2
BMU 3
BMU 4
RVA47.320
Display of plant type
35
Heating curve (line 17)
2.5...40
Pump function Q1 (line 95)
1 (heating circuit pump)
Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
L
N
Q1
F1
N1
Q3
B3
B3
B9
B7
B70
M
L
N
23
79A
31
MB
LPB
MD
A6 / BMU
PPS
DB
B10
B
M
B
M
H1
B10
B
M
B9
B
M
A6
B
M
H1
For a detailed legend, refer to page 158.
Note
Hydraulic circuit
Important
Electrical connections
Legend