103/166
Siemens Building Technologies
Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Description of the heating engineer settings
15.07.2002
4.57 Central
standby
switch
•
Central operation of the interconnected system
From the master controller, the entire heating system can be switched to standby.
1. Press the operating line selection buttons to select operating line 147.
2. Press the + / - buttons to select central standby switching.
Setting range
Unit
Factory setting
0 / 1
Increment
0
Setting 1 (central effect) is active only if the controller has been defined as a master
controller (setting on line 140 = 1).
Entry:
0
Central standby switching is deactivated
1
Central standby switching is activated
If central standby on the master controller is switched on, it can only be switched off
again from that controller!
The central standby circuit does not affect d.h.w. heating. This means that the d.h.w. is
heated according to the settings made.
If the function is activated from the master controller, the operating mode buttons
of
all affected controllers in the segment or system will flash.
4.58 Clock
mode
•
Straightforward time synchronization of the controllers in the system
Clock operation is an important setting for time synchronization if several controllers are
interconnected to form one system.
1. Press the operating line selection buttons to select operating line 148.
2. Press the + / - buttons to select clock mode.
Setting range
Unit
Factory setting
0...3 Increment
3
For time adjustment of the controllers connected to the system,
one
device per system
must be set as a
system lock (setting 3)
.
The setting will change the effect of the system time on the controller's time setting
(settings on operating lines 1 to 2).
Entry:
Benefit
Description
Setting
Important
Effect
Important
D.h.w.
Display
Benefit
Description
Setting
Important
Effect