7ML19981BC01
87
InterRanger
DPS300
Use this feature to determine which slope on the selected echo is used by the
Echo Marker Percentage.
1 =
Leading:
The Echo Marker is placed on the leading edge of the selected echo
(preset).
2 =
Trailing:
the Echo Marker is placed on the trailing edge of the selected echo.
3 =
Peak:
the Echo Marker is placed at the peak of the selected echo. The Echo
Marker Percentage (P825) is not used.
Note
The Echo Lock Window (P713) is centered about the position of the Echo Marker.
P830 TVT Type
Use this feature to select the TVT Curve most suited to the material and clarifier.
This feature is automatically altered when Material (P002) is altered.
Do not select “TVT SLOPES” when the “bF or bLF” Algorithm (P820) is selected.
Values:
1 = TVT Short Curved
2 = TVT Short Flat
3 = TVT Long Flat
4 = TVT Long Smooth Front
5 = TVT Long Smooth
6 = TVT Slopes
P831 TVT Shaper
Use this feature to turn the TVT Shaper “on” or “off”.
Turn the TVT Shaper “on” before altering TVT Shaper Adjust. After TVT Shaper
Adjust has been used to modify the TVT Curve (to avoid a false echo or pick up
the true echo), this feature allows the TVT Shaper to be turned “on” and “off” while
monitoring the effect.
echo marker (P826=3)
echo lock window
echo marker (P826=2)
echo profile
95%
50%
5%
5%
50%
95%
echo marker
(P826=1)
echo marker % (P825)