7ML19981BC01
79
InterRanger
DPS300
P731 (G) Auxiliary Reading Key
Use this feature to enable a specific Parameter Value to be monitored in the RUN
mode.
Enter the Parameter Number whose value is to be displayed in the Auxiliary
Reading field when
is pressed in the RUN mode.
(See OPERATION Keypad for RUN mode Auxiliary Reading selection.)
Values:
000 to 999 (preset to Material Measurement, P921)
P732 (G) Display Delay
Use this feature if the Point Number display scrolls too quickly in the RUN mode.
Enter the delay (in seconds) before the display advances to the next Point
Number.
(Point Number display scrolling is independent from transducer scanning.)
Values:
0.5 to 10 (preset to 1.5 seconds)
P733 (G) Scroll Access
Use this feature to select the programming mode parameter scroll access option
desired.
Select:
“off”
to scroll access all operator accessible parameters.
“smart”
to scroll access Quick Start, previously altered, and tagged
parameters.
“tagged”
to scroll access operator tagged parameters only.
Any accessed parameter may be
tagged
or
untagged
by pressing
.
is displayed when a previously tagged or altered parameter is accessed.
Values:
0 = off
1 = smart (preset)
2 = tagged
Peripheral Communication Support Parameters (P740 to P772)
P740 Peripheral Communications
Use this feature to select the DPS300 to communication message format.
Select:
“off”
if the communication port is not used, to increase the DPS300
processing speed.