InterRanger DPS300
54
7ML19981BC01
P051 Max Volume
Use this feature to display the Reading in volumetric units rather than percent.
Enter the clarifier volume between Empty (P006) and Span (P007).
e.g. 1 If the volume = 3650 m3, enter 3650.
e.g. 2 If the volume = 267,500 US gallons, enter 267.5 (1000's of gallons).
Values:
0.000 to 9999
P052 Clarifier Dimension A
Enter the height as depicted if P050 = 2,3,4, or 5, or the length of one end if P050
= 7, in Units (P005).
Values:
0.000 to 9999
P053 Clarifier Dimension L
Enter the length as depicted (excluding both end sections) if P050 = 7, in Units
(P005).
Values:
0.000 to 9999
P054 Level Breakpoints (Universal Volume Calculation)
Enter level breakpoints* (here volume is known) if P050 = 9 or 10.
Values:
0.000 to 9999
P055 Breakpoint Volumes ( Universal Volume Calculation )
Enter the volume* corresponding to each Level Breakpoint entered.
Values:
0.000 to 9999
* to enter a Level Breakpoint or Breakpoint Volume...
1. Press to display the index symbol, .
2. Scroll
(
or
), or direct access the desired Breakpoint.
3. Key in the desired level or volume value.
4. Press. .
Note:
Refer to TECHNICAL REFERENCE / Volume Calculation for breakpoint value
selection.