7ML19981BC01
11
InterRanger
DPS300
By using ultrasonic echo ranging principles with Sonic Intelligence and velocity
compensation, the DPS300 provides outstanding measurement accuracy, up to
1% of range, depending on process conditions.
The distance calculation may be converted to space, material level, material
volume, or remaining capacity. The Reading chosen (and operating data) for each
clarifier is displayed on the
Liquid Crystal Display
(LCD).
The relays and mA outputs may be used as preset (or programmed as desired) to
activate alarms and/or operate remote monitoring equipment and/or process
control equipment.
As well, the DPS300 may be connected to a Milltronics
BIC-II
(Buffered Interface
Converter) to provide RS-232 and/or RS-422 communications for host computers,
Distributed Control Systems, and
special
(capable of operating as a host device)
Programmable Logic Controllers.
Programming can be done locally using the portable programmer keypad, or
remotely through optional Dolphin software or SmartLinx
®
.
•
The programmer transmits the keypad entries via infrared link to the DPS300, and
can be removed when not in use.
•
Dolphin allows programming either through the portable ComVerter and infrared
link or hardwired via the RS-232/485 communication port.
•
SmartLinx
®
provides protocol specific hardware and software for interface with
popular industrial communication systems.