InterRanger DPS300
44
7ML19981BC01
Program Mode Entry
Upon initial power application, the DPS300 displays “OFF”.
To enter the program mode...
1. Ensure the enclosure lid is secured by the 6 captivated screws.
2. Place the infrared programmer in the enclosure lid recess (no wiring or fastening
required).
3. Press
When the program mode is entered after RUN mode operation, all operating data
is retained in memory. Relay status and mA output values are “held” at “last
known” values (unless affected by a parameter alteration or
is pressed) until
the RUN mode is re-entered. The RUN mode is automatically re-entered if the
DPS300 is left unattended in the program mode for an extended period.
Parameter Value Alteration
In the program mode...
1. Press as required to underline the Parameter Number display field and...
a) Key in the desired Parameter Number, (
direct access
) or...
b) Press
or
as required (
scroll access
).
Note:
As preset, Quick Start Parameters, and previously altered parameters may be
scroll accessed.
2. Press as required to underline the Point Number display field and...
a) Key in the desired Point Number, (
direct access
) or...
b) Press
or
as required, (
scroll access
).
Note:
To alter the Parameter Value for all Point Numbers at once, select Point Number
00.
3. With the desired Parameter Number and Point Number displayed key in the
desired Parameter Value and press
Note:
•
Record each Parameter Value alteration on the appropriate PROGRAMMING
CHART for future reference, (especially should complete reprogramming be
required).
•
If Parameter Value alteration is not permitted, access the Lock parameter
(P000) and enter the security code (See Programming Security).