When the Relay Function (P111) is set for:
•
“alarm” (any option other than “pump”), this feature is preset to “OFF”.
•
“pump”, this feature is preset to “dE”.
To select an independent Relay Failsafe option value:
1. Press
to display to the Auxiliary Function symbol,
2. Press
or
, to scroll access the failsafe options.
3. Press
, with the desired option displayed.
Values:
“OFF”
“HOLd”
“dE”
“En”
mA Output Parameters (P200 to P203, P210 to P215, P219)
If DPS300 mA outputs are to be used, alter the following parameters as required.
Otherwise, proceed to OPERATION.
When an mA Output Parameter is accessed, the mA symbol is displayed in the
Point Type field and the mA output number (corresponding to the DPS300
terminals) is displayed in the Point Number field.
P200 mA Range
Enter the desired range of the mA output displayed.
Value:
0 = OFF
1 = 0 to 20 mA
2 = 4 to 20 mA (preset)
3 = 20 to 0 mA
4 = 20 to 4 mA
P201 mA Function
Use this feature to alter the automatic mA output/measurement relationship, if
desired.
The mA Function automatically corresponds to “level”, “space”, or “distance”
based upon Operation (P001). If a Tank Shape (P050) is programmed, the mA
Function automatically corresponds to volume (unless the mA Allocation has been
altered).
Values:
1 = level
2 = space
3 = distance
4 = volume