Modbus ad‐
dress
Data type /
Size (bytes)
Parameter
Description
Default value
(unit)
Value
range
Access
level
4147
String / 32
Sensor Order Number Sensor order number part 3
(MLFB).
Also shown on the device
nameplate
-
-
Read Only
4164
String / 32
Long TAG
Enter a unique TAG name for
the device (up to 32 charac‐
ters)
4180
String / 16
Descriptor
Enter a unique description
for the measurement point
(up to 16 characters)
4188
String / 16
Startup Date
Enter the installation date of
the device
Table C-4
Operating conditions
Modbus ad‐
dress
Data type /
Size [bytes]
Parameter
Description
Default value
[unit]
Value
range
Access
level
2100
Unsigned / 2 Flow Direction
Define positive and negative
flow direction.
Default positive flow direc‐
tion is indicated by the arrow
on the sensor.
Possible selections:
• 0: Negative: The flow is
measured '+' in default
negative direction and '-'
in default positive direc‐
tion.
• 1: Positive: The flow is
measured '+' in default
positive direction and '-'
in default negative direc‐
tion
1
0 to 1
Read /
Write
2130
Unsigned / 2 Process Noise Damp‐
ing
Select process noise damp‐
ing level:
0: 55 ms filtering (Centrifu‐
gal Pump)
1: 110 ms filtering (Triplex
Pump)
2: 220 ms filtering (Duplex
Pump)
3: 400 ms filtering (Simplex
Pump)
4: 800 ms filtering (Cam
Pump)
2
0 Low to 4
High
Read /
Write
Modbus communication FCT010
C.4 Modbus holding registers tables
SITRANS MASS 2100 & FC300 (FCT010/DSL)
Operating Instructions, 06/2020, A5E39788682-AB
163