E3C010 Battery charging module (superseded by E3C011)
61
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
3
Programming switch "S2": Set battery type
To set temperature compensation according to information from the various battery
manufacturers.
Possible battery variants
Programming switch S2
Var.
Battery manufacturer
Battery model
S2-1
S2-2
S2-3
S2-4
0
off off off off
1
on
off off off
2 Varta
Shin-Kobe (Hitachi)
Kobe PSD (Power Storage
Germany)
CF 12-24 (VM 1224)
HP..-12
HP..-12
off
on
off off
3 Genesis
G12V120W15
on
on
off off
4 Sunrise
Panasonic
LCL 12V24S
LCL 12V..P
off off
on
off
5
Phoenix (Korea)
FNC 12..0
on
off
on
off
6 Yuasa
NP..–12B
off
on
on
off
7 Sonnenschein
Dryfit
A212/..G5
on
on
on
off
8 Power–Sonic
PS12..0
off off off
on
9 Hagen
Drysafe
HDS–12..0NB
on
off off
on
10 Sonnenschein
Dryfit
A512/..G5
off
on
off
on
11
ALARMCOM (FIAMM) 1)
FG...
on
on
off
on
12
off off
on
on
13
on
off
on
on
14
off
on
on
on
15
on
on
on
on
”S2” is set to variant 11 (ALARMCOM) at the factory
1) available from index 'CB' onwards
Î
Floating charge voltage as a function of temperature, or for diagrams of the vari-
ous types of battery see page 44
4
Flat cable header "ST1" (26-pin): I-Bus
5
LED indicator block "Power supply status"
yellow
"Power supply fault"
green "Mains
operation"
yellow "Battery
fault"
H501
H502
yellow unused
Indicators vary in meaning according to application:
a) Battery operation
and symmetry moni-
toring
LED ”Power supply fault
–
Input voltage > 31.0 V –> power unit malfunction
–
Battery voltage > 29.5 V or < 25 V –> charger malfunction
–
Charger malfunction
–
Charger shut down (via software function)
–
Temperature sensor open line / short circuit
–
Temperature sensor measures > 55 °C
–
EEPROM check sum error
LED ”Power on”
–
Input voltage > 28.5 V
LED ”Battery fault
–
Battery voltage < 23 V
–
Asymmetry > 1.0 V or fuse F503 blown
–
Possibly cell short circuit
–
Open line to battery or fuse F501 / F502 blown
–
Autom. test to indicate battery presence negative
–
Autom. battery load test negative
b) Battery operation
without symmetry
monitoring
LED ”Power supply fault
–
Input voltage > 31.0 V –> power unit malfunction
–
Battery voltage > 29.5V or < 25 V –> charger malfunction
–
Charger malfunction
–
Charger shut down (via software function)
–
Temperature sensor open line / short circuit
–
Temperature sensor measures > 55 °C
–
EEPROM check sum error
LED ”Power on”
–
Input voltage > 28.5 V