E3X102/103 Master module (supersedes E3X101)
48
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
9
E3X102/103 Master module
(supersedes E3X101)
9.1 Overview
z
Main evaluating unit for the
CS1140
series of fire detection control units with the
function of ”Main CPU”
Î
With small systems the AlgoPilot B3Q... control console can also take over
the function of ”Main CPU”.
z
Processes up to 16 I-Bus modules
z
Various interfaces, control inputs, control outputs and supply outputs
z
Flash-ROM 2MBx8Bit as program memory
z
SRAM for user data and standard text
E3X102: 1MBx8Bit
E3X103: 2MBx8Bit
z
Lithium battery for RAM buffering
z
Integrated battery-charger and monitoring function unit as I-Bus module
z
Integrated emergency operation electronics
z
Integrated ground fault monitoring
z
Card format 366.8 mm x 200 mm
9.2 Application
Processing capacity –> see document 'Planning' (008725 EP7F-Z1)
For larger systems with stations
CC11..
Terminal blocks X15 and X16 (20 terminals each).
With EMI protect.
–
mounted on module chassis
–
for the connection of the prefabricated cable to connection level, or
–
for direct connection of the periphery
Terminal block X17 (20 terminals)
Only for internal connections
.
–
mounted on module chassis
–
for the connection of the prefabricated cable for battery, temperature sensor and
power unit
Battery terminals (+, -, Center tap)
Temperature sensor
mechanical coding
Card chassis
X15
X16
X17