K3I110 LON I/O p.c.b.
226
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
53
K3I110 LON I/O p.c.b.
53.1 Overview
z
In-/output card with 16 programmable control in-/outputs
z
LON-Bus device
z
Max. 32 devices
z
Selectable ground fault monitoring, detected via master module E3X10. (for ap-
plication details –> see chapter 6)
z
Card format 100 mm x 200 mm
z
Equipped with mounting plate
53.2 Application
–
The card communicate (LON-Bus) via converter module E3I040 (LON-/I-Bus)
with the control unit.
53.3 Key
data
Output contacts, NO
Outputs are galvanically isolated, not supervised on open circuit,
short circuit or ground fault
Ratings relay contacts
Max. 1 A / 30 VDC
Inputs
supervised on open circuit, short circuit, deviation and ground fault
Operating voltage
9..45 VDC
min. 24 mA / max. 184 mA *
min. 53 mA / max. 218 mA *
min. 19 mA / max. 171 mA *
per activated relay (at 24 V) 10mA (without LED 9.2 mA)
Current consumption
24 V
9
V
45
V
per input with closed contact max. 0.5 mA
* All relay activated incl. service LED
53.4 Wiring
principle
K3I110
24VDC
K1
X31
X38
16 programmable monitored control inputs
X56
X63
16 programmable control outputs
max. 30V /1A
E3I040
max. length of LON-Bus 1000 m
B3Q580
B3Q590/
595
LON-Bus
K3I050
24VDC
Data bus