B3R050 Parallel indicator terminal (superseded by B3R051)
194
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
46
B3R050 Parallel indicator terminal
(superseded by B3R051)
46.1 Overview
B3R050 AlgoPilot
B3Q…
z
Option to control terminal AlgoPilot B3Q...
z
Allows additional display fields
z
Unit with 2x 12 display fields each with a red and yellow LED
z
Individual allocation of individual display fields
z
Max. 8 B3R050 per operation AlgoPilot B3Q... possible (=max. 192 display
fields)
z
Communication is via a special serial bus
z
Line and device
not
monitored
z
”Lamp test” is contained in the menu function of AlgoPilot B3Q...
46.2 Application
Installation
The parallel indicator terminal B3R050 fits in the following housings:
–
plastic housing ”small” H23G220 (1x B3R050)
–
housing H28G200
with door H28T120 for 4x B3R050
with door H28T130 for 1x B3R050 (and plan compartment)
Positioning
Immediately next to or in the immediate vicinity of the control terminals AlgoPilot
B3Q...
z
May not be installed separate from control terminal AlgoPilot B3Q..
.
z
Cannot
be ’mixed’ with B3R051/K3R070/K3R071/K3R072
46.3 Key
data
Operating voltage
9..45 VDC
Current consumption
at 24 V
at
9
V
at
45
V
quiescent 40 mA
max. 140 mA
quiescent 80 mA
max. 330 mA
quiescent 30 mA
max. 90 mA