23 Fuses
F1
630 mA/T
supply 5 V/12 V
F2
63 mA/T
auxiliary supply ASIC
F5, F6
2 A/T*
Control line alarm horn 1
F7, F8
2 A/T*
Control line alarm horn 2
F9
2 A/T*
unused
F10
2 A/T*
Emergency operation circuit "Silence horn"
F11
2 A/T*
Emergency operation circuit "Common"
F12
2 A/T*
Emergency operation circuit "Fire alarm"
F13, F14
2 A/T*
Supply "Control console AlgoPilot B3Q..." +
F15, F16
2 A/T*
Supply "Control console AlgoPilot B3Q..." –
F17...F25
0,5 A/T*
programmable control outputs "Q1...Q8"
F26
2 A/T*
Supply "Remote transmission"
F27
2 A/T*
Supply "Reserve"
F28...F32
2 A/T*
programmable control inputs "I1...I4"
F501...F503
6,3 A/T*
battery (F501 "Positive" / F502 "Negative" / F503 "Center")