E3G080 Control module ”Extinguishing”
155
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
37.9 Important
components
F11
F13
F14
F16
1
2
3
4
5
6
R61
R60
S3
ST1
S1
S2
H1
H2
H3
H4
7
8
S4
K1
9
10
11
S5
H5
12
13
X2
R151
14
F7
ON
1
ON
1
4
ASIC
I-BUS
µ
P
ON
Legend:
1
Fuses: "F11, F13, F14, F16"
2 A/T Main / sector valve / alarm horn / illu-
minated warning panel (Fuses with high breaking capacity, sand-filled)
2
Resistors "R60/61": Choice of internal resistor sector for the main/sector valve
Two areas can be selected for the monitoring of the valves by inserting or remov-
ing resistors. R60 (71k5) is for the sector valve and R61 (71k5) for the main valve.
R60/61 are inserted at the factory.
–
Valve coil 16...160
Ω
=
R60/61 removed
–
Valve coil 161...320
Ω
= R60/61 inserted
3
Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address
Programming switch S3
Nr.
S3-1 S3-2 S3-3 S3-4 S3-5
S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number 1
on
off off off off
off
2
2
off
on
off off off
off
3
3
on
on
off off off
off
4
4
off
off
on
off off
off
5
5
on
off
on
off off
off
6
6
off
on
on
off off
off
7
7
on
on
on
off off
off
8
8
off
off
off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off
off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
"S3-1...6" are set to "off" at the factory