B3Q6.. / 565 Control terminal AlgoPilot
184
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
43.7 Connections
Supply I-Bus modules
3
2
1
+
+
Plug-in terminals ”orange”
K1
24V
5V
to the I-Bus modules
serves with ” CI ” at the same
time also as input of E3C011
1
2
1
Plug-in terminals ”orange”
K4
Operat.enabled
C
external operation
enabled
1
2
3
4
1
Plug-in terminals ”grau”
K5
C-Bus
B1
A1
B2
A2
1
2
3
1
Plug-in terminals ”orange”
K6
Emergency
operation
C
F3
Fire alarm
F4
Switch off horn
1
2
3
4
5
6
+
-
+
-
1
Plug-in terminals ”orange”
K7
F2
F1
3
2
8
9
10 14 15
+
-
-
+
E3X10.
Possibly additional control
terminals B3Q...
4
Terminal block
X16
4
-
12
13
7
6
blue
blue
green
red
3)
External key switch
GND
-
-
Supply 1
Supply 2
1
2
3
4
1
Plug-in terminals ”orange”
K2
C
B3Q6../565
2)
Inputs TROUBLE
power supply
(default = not active)
Emerg. power
Power supply
Battery
Local power supply
(internal only)
1) 4)
5)
1) C C-Bus must
always
be wired as a loop line (even with built-in control terminal AlgoPilot B3Q...)
2) Configuration as in-/or output see jumpers X31, X32, X33, X34, Y31, Y32, Y33, Y34 on page 183
3) For application as "CI", external control terminals ("CT") are connected on K7
4) Cabling C-Bus: max. 1000 m per loop with Ø 0.6 mm wire
max. 1400 m per loop with Ø 0.8 mm wire
((always including return line) for cable type (impedance adaptation) see page 182
5) "Cabling principle AlgoPilot B3Q..." –> see page 23