E3M120 Line module ”CBA8000/TS9000”
104
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
25
E3M120 Line module ”CBA8000/TS9000”
25.1 Overview
[First production series of E3M120 (without index identification) were manufactured in Norway. The
designations used on these boards, which were not confirming to official Swiss production standards
used today, are still indicated in square brackets in this chapter.]
z
Line module for
CBA8000/TS9000 detectors
z
I–Bus module with one IB processor and one line processor
z
Designed for
4 loop lines (no stub lines)
z
Line inputs protected against over voltage
z
Main card format 100 mm x 200 mm; Daughter card format 100 mm x 160 mm
z
I-Bus address is set at programming switch ”S1”
25.2 Key
data
Addresses per line
...119
Number of wires
2
Twisted cable
not necessary
Line resistance
...30
Ω 1)
Line capacitance
...100 nF 1)
Short-circuit proof line
yes (separate isolator device available)
Quiescent current at 24 V
8.5 mA + 1.3 mA per D-Bus user
Quiescent current at 5 V
65 mA
Terminal block J4 (20 terminals)
–
mounted on module chassis
–
for the connection of the prefabricated cable to connection level, or
–
for direct connection of the periphery
Card chassis
–
mounted on module chassis
25.3 Special
functions
Line separator
Upon short circuit the part of the line which malfunctions must be separated from
the rest of the line. This is carried out by line separators integrated in each detec-
tor, manual call point and input/output module. According to EN54, a ”simple error”
may not cause the malfunction of more than 32 detectors. After the short circuit the
line automatically reverts to ”Normal operating condition”.