E3L030 Control module VdS (VdS module)
134
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
3
LED indicator block
yellow
"Emergency operation E3L030 or E3X... or AlgoPilot B3Q..."
green "Activate
unlocking"
yellow "Activate
extinguishing"
red "Activate
ÜE"
H2
H1
4 0
Ω
resistor "X12": For the allocation of "LED4" active when the E3L030 is in
emergency operation mode (LED4 is provided as a "spare" in FBF).
0
Ω
resistor "X12"
inserted
: LED 4 is active when E3L030 is in emergency
operation mode (fault)
0
Ω
resistor "X12"
not inserted
(factory set)
5
Flat cable header "ST1" (26-pin): I-Bus
6
Fuse: 'F31' 2 A/T Module supply (Fuse with high breaking capacity sand-
filled)
7
Plug-in terminals "K1": Supply for "I-Bus" modules
8
Programming switch "S3": Setting "I-Bus address"
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address
Programming switch S3
Nr.
S3-1 S3-2 S3-3 S3-4 S3-5
S3-6
0
Module out of commission (unused) 1)
off
off
off
off
off
off
1
I-Bus user number 1
on
off off off off
off
2
2
off
on
off off off
off
3
3
on
on
off off off
off
4
4
off
off
on
off off
off
5
5
on
off
on
off off
off
6
6
off
on
on
off off
off
7
7
on
on
on
off off
off
8
8
off
off
off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off
off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
"S3-1...6" are set to "off" at the factory
1) E3L030 functions in "emergency operation" with I-Bus address 0
32.5 Special
functions
Emergency operation
An alarm which occurs during system malfunction (emergency operation) can still
be handled via FBF and ÜE and FSD can also still be activated.
Function overview during ”emergency operation”
Function Emergency
opera-
tion E3L030
Emergency opera-
tion CPU
FBF
Indicator ”ÜE activated”
●
●
Indicator ”LEDs 5, 6, 7, T5 operational”
–
●
Function ”Silence audible signal”
●
●
ÜE
Function ”Activate ÜE”
●
●
FSD
Function ”Activate FSD unlocking”
●
●
SST
(Extinguishing standard interface)
– –
TK