E3G060 Control module ”monitored” (Part No 460514)
140
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
34.4 Important components (Part No 460514)
H1
H6
F19
S2
ST1
S3
S6
K1
1
4
1
1
ON
ON
ON
1
2
3
4
5
6
7
8
ASIC
I-BUS
F1
F12
Legend:
1
Emergency operation –> Programming switch "S6": Allocation activation by
"Emergency operation mode"
If required, the 6 control lines can also be activated even if an alarm is given during
system malfunction (emergency operation). This function can be selected for each
control line via the "S6" programming switch.
Affiliation:
"S6-1" = Control line 1...
"S6-6" = Control line 6
"
OFF
" Position = Control line is activated in "Emergency operation mode"
2
Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address
Programming switch S3
Nr.
S3-1 S3-2 S3-3 S3-4 S3-5
S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number 1
on
off off off off
off
2
2
off
on
off off off
off
3
3
on
on
off off off
off
4
4
off
off
on
off off
off
5
5
on
off
on
off off
off
6
6
off
on
on
off off
off
7
7
on
on
on
off off
off
8
8
off
off
off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off
off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
"S3-1...6" are set to "off" at the factory