E3M060 Line module ”MS9i”
80
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
18.3 Important
components
ca.30
ASIC
I-Bus
µ
P
S3
ON
1
ST1
ST10
K1
1
4
F3
F4
F5
F6
1
2
3
4
5
6
Legend:
1
Programming switch "S3": "I-Bus address setting"
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address
Programming switch S3
No.
S3-1 S3-2 S3-3 S3-4 S3-5
S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number 1
on
off off off off
off
2
2
off
on
off off off
off
3
3
on
on
off off off
off
4
4
off
off
on
off off
off
5
5
on
off
on
off off
off
6
6
off
on
on
off off
off
7
7
on
on
on
off off
off
8
8
off
off
off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off
off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
"S3-1...6" are set to "off" at the factory
2
Flat cable header "ST1" (26-pin): I-Bus
3
Connector "ST10": Mimic display (active only with "Emergency alarm")
4
Plug-in terminals "K1": Power supply for modules "I-Bus"
5
Fuse 'F7' 1.6 A/F Module supply (SMD fuse can only be changed at factory)
6
Fuses: 'F3...F6' 0.5 A/T MS9i line (Fuses with high breaking capacity,
sand-filled)