K3R072 Mimic Display board (supersedes K3R071)
212
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
50
K3R072 Mimic Display board
(supersedes K3R071)
50.1 Overview
z
Option to control console AlgoPilot B3Q..., or to LON/Mimic Display converter
K3I050
z
2x24 outputs for LED activation for Mimic Display panels, or not monitored relay
contacts (K3G060)
z
2 control outputs for local ’Buzzer’ and ’LED operation’
z
2 inputs for ’Switch-off buzzer’ und ’Lamp test’
z
The lamp test is integrated in menu function AlgoPilot
z
Individual allocation of the individual outputs
z
Max. 24 units, however max. 8 addresses
z
Communication is via a special serial bus
z
Line and device not monitored
50.2 Application
The Mimic Display board is built into the mimic panel housing.
–
Connection to LED via flat cable F50F410 (50-wire, 24 red LEDs, cable length
1 m, must be ordered separately)
–
The relay card K3G060 can be connected instead of LEDs
–
Line length data bus AlgoPilot –> K3R072 max. 1000 m
Connection line
–
Data bus:
via flat cable or 6-wire cable
–
Supply 24 V:
via 3-wire cable
Short-circuit proof in-/outputs only for
inside
housing appli-
cation
Synoptic display panel housing
AlgoPilot
max. permissible length of the data bus 1000 m
1) LED 1…24 –> wires 49+50 for 'LED operation'
2) LED 25…48 –> wires 49+50 unused
3) Key 'Switch-off buzzer'
4) Key 'Lamp test'
5) Buzzer
1
2
3
4
5
6
6) Use Z3I520
These in-/outputs can be in
parallel with other K3R072 if
located in same cabinet
50.3 Key
data
Operating voltage
9..45 VDC
Current consumption
at 24 V
at 9 V
at 45 V
quiescent 40 mA
max. 140 mA
quiescent 80 mA
max. 330 mA
quiescent 30 mA
max. 90 mA