MS-700AP(U) Series

Fire Alarm Manual Station

1

Mircom’s MS-700AP(U) Series Fire Alarm Manual Stations 
provide manual fire alarm activation. These high quality, die-cast 
metal stations are available as single or dual-action devices. Each 
station has a permanently attached AP addressable module, 
which has a pair of dials for setting the address.

Specifications & Dimensions

Compatible with Mircom Fire Alarm Control Panels
Electrical Rating:

Dimensions:

MS-702AP: 4.93” H x 3.56” W x 2.56” D
MS-710AP(U): 4.93” H x 3.56” W x 2.9” D

Converting Double Action Manual Stations to Single 
Action (MS-710AP(U) only):

1.

Using a reset key, unlock and open the manual station.

2.

Remove the smaller two screws and accompanying 
brackets fastening the PUSH bar.

3.

Hold the manual station vertically with one hand with the 
keyhole at the bottom. Tilt the manual station towards 
you and remove the PUSH bar.

Installing the manual station

This guide covers these models:

MS-702AP Intelligent Two Stage Manual Station AP
MS-710AP(U) Intelligent Dual Action Manual Station AP
The suffix 

U

 indicates a USA version.

Contents of kit

MS-702AP: 4 mounting screws, 2 reset keys (black), 2 stage two 
keys, 1 glass rod

MS-710AP(U): 4 mounting screws, 2 reset keys (black), 1 glass 
rod

A. Wiring

Note:

The maximum wire size is 12 AWG.

1.

Connect the black (-) wire from the previous station to 
the terminal that is connected to the black (-) wire from 
the addressable module.

2.

Connect the black (-) wire leading the next station to the 
other side of the terminal that is connected to the black
(-) wire from the addressable module. 

Note:

The wires must be on opposite sides of the set screw.
Refer to Figure 2 for the location of the wires.

3.

Tighten the (-) terminal.

4.

Connect the red (+) wire from the previous station to the 
terminal that is connected to the red (+) wire from the 
addressable module.

5.

Connect the red (+) wire leading to the next station to the 
other side of the terminal that is connected to the red (+) 
wire from the addressable module.

Note:

The wires must be on opposite sides of the set screw.
Refer to Figure 2 for the location of the wires.

6.

Tighten the (+) terminal.

MS-702AP

MS-710AP(U)

Nominal Operating Voltage: 
15-32 VDC

Nominal Operating Voltage: 
15-32 VDC

Maximum alarm current @ 24V: 
5.4 mA

Maximum alarm current @ 24V: 
600 µA

Average operating current @ 
24V: 600 µA

Average operating current @ 
24V: 400 µA

Notes

• Wire as shown so that supervision of connections is 

maintained.

• Maximum wire size: 12 AWG
• ADA compliant.
• To be installed per ADA 4.27.1 to 4.27.4 inclusive.
• All manual fire alarm stations shall be installed as per 

the specific requirements outlined in the UL/ULC codes, 
as well as all other applicable national or local codes. 
Final acceptance is subject to the local authority having 
jurisdiction.

Screws

Screws

Figure 1: Wiring Diagram

TO ADDRESSABLE
MODULE

WRONG: BOTH 
WIRES ON THE 
SAME SIDE AS 
THE SET SCREW

TO ADDRESSABLE
MODULE

CORRECT: BOTH 
WIRES ON
OPPOSITE SIDES 
OF THE SET SCREW

X

Figure 2: Close-up of terminals showing correct wiring

FROM

TO NEXT STATION OR 
END OF LINE DEVICE

-

  BLACK

+

 RED

}

-

-

+

+

ADDRESSABLE
MODULE

PREVIOUS
STATION

}