09.02
Parameter List
Siemens AG 6SE7087-6AK85-1AA0
5-27
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
5.11 Analog
input/output
P655 CUR
AnaOutActVal
Number of the parameters whose value is to be output at the analog output
of the CUR, (terminal X102-14).
PNU=28FHex; Type=O2; Scaling: 1Hex
=
∧
1
0 to 999
-
37
2/ BR
2/ BR
P656
CUR AnaOut Gain
Gain for the analog output of the CUR (terminal X102-14)
P656 = desired analog output voltage at PWE=100%, if offset=0
The output voltage is calculated with the following formula:
U(out)= [(PWE/100%)
*
P656] + P657
PNU=290Hex; Type=I2; Scaling: 1Hex
=
∧
0.01 V
±
320,00
[V]
-
10.00
2/ BR
2/ BR
P657 CUR
AnaOutOffset
Offset for the analog output on the CUR (terminal X102-14)
The analog output can represent voltages of -10V to +10V.
PNU=291Hex; Type=I2; Scaling: 1Hex
=
∧
0.01 V
-100.00 to 100.00
[V]
-
0.00
2/ BR
2/ BR
P658
*
AnaOut Conf Curr
Configuration of terminal X102-16 (actual current display)
0
Output with correct sign
(positive voltage: motoring current)
(negative voltage: regenerative current)
1
Output absolute value (positive voltage only)
2
Signed output, inverted
(positive voltage: regenerative current)
(negative voltage: motoring current)
3
Output of absolute value, inverted (negative voltage only)
PNU=292Hex; Type=O2; Scaling: 1Hex
=
∧
1
0 to 3
signed
absoluteVal
inverted
inv. absVal
-
0
2/ BR
2/ BR
P660 SCI
AnalogInConf
Configuration of the SCI analog inputs; defines the kind of the input signals
Parameter values
Terminals
Terminals
X428/3, 6, 9
X428/5, 8, 11
0:
-10 V ... + 10 V
- 20 mA ... + 20 mA
1:
0 V ... + 10 V
0 mA ... + 20 mA
2:
4 mA ... + 20 mA
Notes:
Only one signal can be wired per input; alternatively voltage or current
signals can be evaluated.
Voltage and current signals must be connected to different terminals.
Settings 1 and 2 only allow unipolar signals, i. e. the internal process data
are also unipolar.
At setting 2 an input current < 2 mA causes a fault trip (broken wire proof)
The offset scaling of the analog inputs is done via P662.
i001: Sl11
Slave 1, analog input 1
i002: Sl12
Slave 1, analog input 2
i003: Sl13
Slave 1, analog input 3
i004: Sl21
Slave 2, analog input 1
i005: Sl22
Slave 2, analog input 2
i006: Sl23
Slave 2, analog input 3
Condition:
The related SCB board must be reported via P090 and P091, respectively
PNU=294Hex; Type=O2; Scaling: 1Hex
=
∧
1
0 to 2
6
0
3/ BR
3/ BR