09.02
Start-Up
Siemens AG 6SE7087-6AK85-1AA0
4-41
Rectifier/Regenerating Unit Operating Instructions
4.3.9.5
Drive setting (P052 = 5)
This function is used to change the drive setting(rectifier/regenerating data, system data).
This includes all parameters that can be written in the "Drive setting" status ("A" ,see right-hand column of the
parameter list in Chapter 5).
Once you have completed the drive setting procedure, you can decide whether to implement the function
selection "Forming" (P052=20) or "Circuit identification" (P052 = 21) or whether just to reset the status (P052 =
0).
"Drive setting" can be selected in the following statuses: "Switch-on inhibit", "Ready-to-switch-on" or "Fault".
Procedure:
⇓
P052 = 5
Function selection
Drive setting
⇓
P051 = 3
Access stage Expert mode - (if all parameters, which can be accessed in the
"drive setting" status (A) are required)
⇓
All parameters, which can be written into the "drive setting" (A) status (see
right-hand column of the parameter list in Chapter 5), can be changed.
⇓
if
necessary
⇓
P052 = 20
Function selection " Forming "
(refer to Section 4.3.9.6)
⇓
P052 = 21
Function selection " Circuit identification "
(refer to Section 4.3.9.7)
⇓
P052 = 0
Return
⇓
The display appears (r000) while parameters and internal variables are being
de-assigned, depending on the function selected.
⇓
The "Switch-on inhibit" (008) or "Ready-to-switch-on" (009) operating display appears after the
selected function or selection has been completed